Negative and positive differential pressures
Provide the range and the pressure differences actually used, including negative values if the ports see reverse differential. If the instrument stores minima or peaks, distinguish those functions from a steady display comparison at the working points.
During balancing work, a technician may reverse the hoses to read a small negative room pressure. Include that orientation and sign in the record. Taking the magnitude alone can hide a port reversal when the room is handed back to operations.
Specifications and service checks
A service log that exports pascals may be compared with a display in millibar. Since 1 mbar equals 100 Pa, an entry of 2.5 mbar corresponds to 250 Pa. Recording the selected port and unit avoids a hundredfold transcription error.
- Range and configuration
- Small differential pressures are commonly quoted in Pa, hPa or inches of water. One hPa is 100 Pa.
- Manufacturers and models
- Testo 510 is a portable differential pressure meter with a 0–100 hPa range. Identify both hose connections and the direction used.
- What we check
- Check the display in its working units and record the reference type. A differential sensor can be checked with both signs of pressure difference; an absolute model needs an absolute reference.
- Reference equipment and accuracy
- Use a calibrated low-pressure standard. Leaks and vertical differences between reference ports become significant near zero.
- When to repeat the check
- Monitor zero after transport and reassess after overpressure or liquid entering a gas-only meter.
Technical references testo 510 set - differential pressure measuring instrument