On this page
Humidity span and transmitted output
Give the lower and upper values assigned to the output and the paired humidity and temperature conditions. Keeping humidity indication, transmitted signal and configured scaling together helps trace a disagreement seen only on the control-room screen.
A room display and a building-management channel can report different values because they use different scaling. Identify the humidity at the sensor, the signal at the transmitter terminals and the value shown by the receiver. Those three records help locate a discrepancy along the installed loop.
Specifications and service checks
A transmitter configured for 0–100 %RH over 4–20 mA would ideally produce 12 mA at 50 %RH. If the panel disagrees, record the current at the transmitter and the percentage at the panel. The two figures help identify which part of the signal path needs checking.
- Range and configuration
- Vaisala’s HMP110 is specified over 0–100 %RH. A configured analogue output may represent only a selected part of that span; note both endpoints and the engineering units.
- Manufacturers and models
- The Vaisala HMP110 family includes probes with analogue outputs; the data sheet identifies the sensor and available signal options.
- What we check
- Run a comparison at the agreed humidity and read the transmitted electrical or digital value. For analogue outputs, retain the programmed humidity-to-output scaling with the result.
- Reference equipment and accuracy
- A traceable reference hygrometer establishes the input. A calibrated electrical readout is also needed when the result is expressed in mA or volts.
- When to repeat the check
- Exposure near saturation and chemical contamination affect drift. Review intermediate checks at a representative point after exposure or replacement.
Technical references Vaisala HMP110 specifications · NIST humidity measurement services