On this page
Take the settings from the working loop
Copy the lower and upper configured values, pressure unit and output type from the working setup. Mark the high and low connections against the plant tag. The sensor limits on the nameplate may be wider than the span used on the line.
Level installations and remote seals
For a tank level service, include the process drawing or the expected differential pressure at empty and full. Those values need not start at zero. Say whether the transmitter uses a manifold, remote seals or capillaries and whether the job concerns the installed assembly. The physical arrangement helps explain offsets that are intentional.
Match input points to the output being read
For each test point, pair the applied pressure with the expected output and unit. If the job includes the control room, provide the receiving channel tag so the technician can record the transmitter and panel readings at the same point.
Differential pressure transmitter
If a differential transmitter measures tank level using a wet leg, include the configured lower range value. The transmitter can be correct at zero differential while the plant range starts at a different applied pressure.
Consider a zero-based 4–20 mA transmitter at a quarter of its differential-pressure span. A linear pressure output gives 8 mA. A square-root flow output gives 12 mA because a quarter of the pressure span represents half the flow span. Knowing whether the transmitter or the control system performs that conversion resolves a surprisingly large apparent discrepancy.
| Configured output | What to request |
|---|---|
| Linear in differential pressure | Specify pressure points and loop current. If the control room displays flow, identify the receiving channel that performs the conversion. |
| Square-root extraction in the transmitter | Specify pressure points and the expected flow-scaled output. Check the receiving channel’s configuration before comparing the two indications. |
- Range and configuration
- Specify the sensor limits and the configured lower and upper values separately. On a linear 4–20 mA range, the mid-span output is 12 mA, even when zero pressure is outside the configured span.
- Manufacturers and models
- Emerson's Rosemount 3051 family includes differential, gauge and absolute versions with several output options. Use the complete model code.
- What we check
- Compare known pressures with the analogue or digital process value actually used. Record the configured transfer characteristic and distinguish the as-found and adjusted results.
- Reference equipment and accuracy
- Use a traceable differential standard and account for static line pressure where the application requires it. A common change on the two ports can affect the result even when the differential stays fixed.
- When to repeat the check
- Review the interval against drift in the working range. Check again after a sensor change, rerange or repair when it affects the reported value.
Technical references Product Data Sheet: Rosemount 3051 Pressure Transmitter · Rosemount guide to differential-pressure flow measurement