On this page
Supply and extract readings
A supply terminal and an extract terminal send air through the hood in opposite directions. Give the usual flow for each and identify any correction selected in the meter. This lets a commissioning engineer compare the certificate with the instrument configuration used in the room.
A grille smaller than the hood opening and a grille larger than it present different arrangements on site. Tell us the dimensions of the fitted hood and whether the instrument applies a correction for the terminal used. If a separate pressure base or different hood is shared across jobs, identify that pairing on the request.
Air flow hoods
Include the diffuser type or arrangement relevant to the requested work. A hood changes the measurement configuration, so a detached sensor result may not describe the assembled kit. RTS compares the assembled hood’s flow indication with a reference, recording the frame, correction mode and accessories used.
Specifications and service checks
A square supply grille had a rectangular adapter fitted for the last balancing visit. Record the adapter opening and the hood orientation with the result. If facilities now want a reading at an extract grille, identify that as a second direction when booking the comparison.
- Range and configuration
- The TSI 8380 hood covers 42 to 4,250 m³/h. This figure applies to volume through the hood. A probe connected to the same meter has a separate air-speed range.
- Manufacturers and models
- Two examples are the TSI AccuBalance 8380 and the Alnor EBT731 capture hood.
- What we check
- Compare the complete hood with a reference airflow bench at points used for supply or extract. Identify the fabric hood, frame and meter fitted during the comparison.
- Reference equipment and accuracy
- Use a traceable volume-flow reference whose uncertainty covers the agreed low-flow point. Leaks and hood back-pressure can outweigh display resolution.
- When to repeat the check
- Review the interval against the last comparison and frequency of field use. A torn canopy, replacement frame or pressure sensor repair warrants a fresh check.
Technical references TSI AccuBalance 8380 specifications · TSI Alnor instrument catalogue