Air flow hood calibration

A capture hood measures the air volume passing through a grille. Its fabric hood, frame and measuring base make up the assembly, so the opening size and flow direction belong on the job sheet alongside the base serial number.

Send an enquiry
Air flow hood — equipment illustration
Equipment illustration
On this page

Supply and extract readings

A supply terminal and an extract terminal send air through the hood in opposite directions. Give the usual flow for each and identify any correction selected in the meter. This lets a commissioning engineer compare the certificate with the instrument configuration used in the room.

A grille smaller than the hood opening and a grille larger than it present different arrangements on site. Tell us the dimensions of the fitted hood and whether the instrument applies a correction for the terminal used. If a separate pressure base or different hood is shared across jobs, identify that pairing on the request.

Air flow hoods

Include the diffuser type or arrangement relevant to the requested work. A hood changes the measurement configuration, so a detached sensor result may not describe the assembled kit. RTS compares the assembled hood’s flow indication with a reference, recording the frame, correction mode and accessories used.

Specifications and service checks

A square supply grille had a rectangular adapter fitted for the last balancing visit. Record the adapter opening and the hood orientation with the result. If facilities now want a reading at an extract grille, identify that as a second direction when booking the comparison.

Range and configuration
The TSI 8380 hood covers 42 to 4,250 m³/h. This figure applies to volume through the hood. A probe connected to the same meter has a separate air-speed range.
Manufacturers and models
Two examples are the TSI AccuBalance 8380 and the Alnor EBT731 capture hood.
What we check
Compare the complete hood with a reference airflow bench at points used for supply or extract. Identify the fabric hood, frame and meter fitted during the comparison.
Reference equipment and accuracy
Use a traceable volume-flow reference whose uncertainty covers the agreed low-flow point. Leaks and hood back-pressure can outweigh display resolution.
When to repeat the check
Review the interval against the last comparison and frequency of field use. A torn canopy, replacement frame or pressure sensor repair warrants a fresh check.

Technical references TSI AccuBalance 8380 specifications · TSI Alnor instrument catalogue

Enquire about Air flow hood