On this page
The datum for start and stop levels
In a sump, the start and stop levels are useful only when both heights are measured from the same point. Is that point the tank floor or the mounting flange? Mark it on a sketch, with the float orientation and the liquid in service. The contact can change before the pump starts if the controller has a delay. For that reason, use the switch contact itself to describe the event you want recorded.
Float switches
Give the required operating and reset levels from a named datum, with the intended liquid and mounting orientation. An electrical contact check alone does not establish the liquid level at operation. RTS measures switching and reset levels with the specified liquid, mounting and contact arrangement.
Specifications and service checks
On a suspended cable float, changing the clamped cable length can change the separation between operating levels. Include the mounting arrangement and free cable length when asking about a replacement that starts a pump at a different level.
- Range and configuration
- Specify the switching height from a fixed datum, the float orientation and the minimum liquid density. A switching point can differ on filling and draining.
- Manufacturers and models
- WIKA FLS float switches may have multiple contacts. Identify each contact and its position along the stem.
- What we check
- Observe each contact change as the liquid level rises and falls. Record the height and contact identification at both events.
- Reference equipment and accuracy
- Use a calibrated height scale or level reference and a contact-state monitor, with a liquid appropriate for the float.
- When to repeat the check
- Repeat after float or stem replacement or a change in the density of the process liquid.
Technical references Float switch - FLS - WIKA USA