Flow transmitter calibration

A flow transmitter translates the signal of a primary sensor into a process indication or output. Some units retain a sensor-specific calibration factor, while others work from a user-entered range.

Send an enquiry
Flow transmitter — equipment illustration
Equipment illustration
On this page

Relating loop current to the flow range

In a water line scaled linearly from 0 to 100 m³/h at 4–20 mA, 12 mA represents 50 m³/h. That is a useful electronics check, but a different input law or a sensor-specific factor changes the relationship. A photo of the configured range and the sensor nameplate will help us identify which conversion your installation uses. Mark whether the sensor, transmitter and receiving indication are all part of the job.

Flow transmitters and the sensing element

List both identities, the signal output, configured span and any density or temperature compensation settings. Ask whether the requested result covers the electronics alone or the complete assembly with flowing medium. Include the application fluid and relevant operating conditions. This lets RTS review the correct method rather than assign a full flow result to an electrical simulation.

Specifications and service checks

On a skid with both a pulse total and a current loop, the operator may see a plausible instantaneous rate while the daily total disagrees. Provide the pulse factor and analogue scaling together. The two outputs can represent the same fluid movement in different ways.

Range and configuration
On a 4–20 mA output, the current endpoints correspond to two configured flow values. The same hardware may instead supply a pulse total or digital reading.
Manufacturers and models
Emerson's Micro Motion 2700 transmitter can produce a scaled output from a compatible sensor.
What we check
Compare output with the configured input or flow at several points. Identify whether the result includes the sensor, transmitter alone or output conversion only.
Reference equipment and accuracy
A calibrated meter or pulse counter verifies transmission. A complete flow comparison requires an independently measured quantity of fluid.
When to repeat the check
Recheck scaling after a configuration download, sensor substitution or change of pulse weight.

Technical references Installation Manual: Micro Motion 1700 and 2700 Transmitters