Mapping the terminal input to the panel scale
Supply the terminal diagram, input range and display endpoints. If the meter drives alarms or a retransmitted output, identify those functions separately. A photograph of the installed engineering-unit label helps match the result to the operator’s screen.
A display scaled from 0 to 200 units for a linear 4–20 mA input should show 100 units at 12 mA. If its endpoints have been changed during a plant modification, use the new settings when interpreting this midpoint.
Specifications and service checks
A readout for load or pressure may display an alarm symbol before its numeric reading reaches full scale. If the issue is an alarm, supply the displayed number and contact state together. The numeric scaling and the programmable alarm setting can be checked individually.
- Range and configuration
- For example, a display scaled 0–100 from 4–20 mA should read 50 at 12 mA when linear scaling is selected.
- Manufacturers and models
- Rishabh's RISH VISTA panel-meter series includes direct-reading electrical meters. On a programmable process meter, record the input type and scaling separately.
- What we check
- Compare electrical input and displayed value across the scale, including the working point. Record the display settings and any alarm thresholds under review.
- Reference equipment and accuracy
- Use a traceable current or voltage source for the programmed input. A shunt or transformer must be included if its contribution is needed.
- When to repeat the check
- Verify after a range, transformer-ratio or decimal-point change.
Technical references 212, 312 and 412 RISH VISTA Series Analog Panel Meters