Injection current combinations and timing
Identify the current range, frequency, output combinations and timer function used. Include the normal leads or reference sensor where they define the configuration. Specify steady current, test duration and the event used to stop the timer for the requested result.
A breaker trip time includes the breaker response as well as the timing measurement. For a question about the kit’s timer, identify the electrical start and stop signals so that an instrument check is not mistaken for a complete breaker performance test.
Specifications and service checks
Current delivered by the kit depends on the connected path, especially at high current. If the unit fails to reach a requested current only on a particular switchgear assembly, note the path and approximate burden as well as the current setting.
- Range and configuration
- State test current, duration and duty rating. A short-duration high output is a different condition from a sustained thermal test.
- Manufacturers and models
- Megger ODEN AT is a primary current injection system. Its available current depends on the selected units and the impedance of the connected circuit.
- What we check
- Compare indicated current with an independent reference over the required band and verify the timer against a known interval or contact event.
- Reference equipment and accuracy
- Use a calibrated high-current transformer or suitable shunt and a traceable timer. Include waveform and heating effects at the selected current.
- When to repeat the check
- Reassess after changing the high-current leads, current module or timer input.
Technical references ODEN AT primary current injection test system