Identify the modes used by the electrician, the current multiplier and any phase selection. State whether you need the output current, timer or ramp measurement checked. A bench result on the tester is distinct from a site test of an installed protective device.
A test record can contain both a result in milliseconds and a result in milliamperes. One describes elapsed time, the other a current. If electricians use a timed trip test and a ramp function, name both on the order and keep the units visible on the result sheet.
RCD testers and trip measurements
Include any ramp or automatic sequence used by the technician. These functions need an appropriate simulator or reference arrangement; a stopwatch check alone does not evaluate the complete tester. RTS checks the selected trip modes and retains their settings with the results.
Specifications and service checks
An RCD installation can trip differently for different residual-current waveform types. When investigating a tester, identify the waveform setting and any polarity or phase option in the stored programme. A leakage-current value by itself leaves those conditions unspecified.
- Range and configuration
- Common settings such as 30 mA identify nominal residual current. Trip current in milliamperes and trip time in milliseconds are distinct results.
- Manufacturers and models
- Fluke 1664 FC includes residual-current-device tests for specified RCD types. Identify the waveform and rated residual current used at site.
- What we check
- Verify the test current produced at selected settings and the indicated time for a characterised trip event. Record ramp and fixed-current modes separately where used.
- Reference equipment and accuracy
- Use a suitable calibrated RCD test-instrument verifier or current and timing standards that support the waveform and phase settings concerned.
- When to repeat the check
- Verify after lead repair or a switch in working modes. Keep the instrument calibration distinct from the site's RCD inspection schedule.
Technical references Fluke 1660 series RCD test specifications