Relay input channels and timer events
Provide the channel combinations, nominal input ratings, frequency and phase angles from the relay test routine. Identify timer start and stop conventions. Separate the calibration results for the injection kit from the relay settings and response observed at the plant.
A relay may use a phase comparison between two channels rather than the magnitude of one current alone. When commissioning relies on that comparison, include a paired-channel result at the relevant phase displacement in addition to individual current readings.
Specifications and service checks
A relay’s displayed operating time may include a delay set in its own logic. A test kit measures until it sees the chosen contact or output change. Naming that endpoint helps distinguish a timing-channel check from the protection relay’s overall response.
- Range and configuration
- Set out RMS voltage, current, frequency, phase and timing requirements. Simultaneous loading of channels can matter to their output capability.
- Manufacturers and models
- OMICRON CMC 356 is a secondary injection test system with synchronised voltage and current outputs. Identify channels and wiring configuration.
- What we check
- Compare each secondary current or voltage output, including relative phase when multiple channels drive a relay. Use a known contact event to check the timing input independently.
- Reference equipment and accuracy
- Use reference voltage, current, phase and time measurements appropriate to the selected outputs. Channel synchronisation belongs in an end-to-end timing result.
- When to repeat the check
- Confirm reference outputs after channel repairs or software changes affecting signal generation.
Technical references OMICRON CMC 356 relay test set