Leading and lagging indications
Give the display quantity, voltage, current, frequency and phase arrangement used in the plant. Include leading and lagging points where the meter controls compensation. A result near unity alone gives limited information about the lower power factors used to switch capacitor stages.
A display reading 0.8 can refer to a leading or lagging load. Those two conditions can call for different actions at a capacitor bank. If the instrument uses a symbol or direction lamp, include its state alongside the number when recording the comparison.
Specifications and service checks
Under nonsinusoidal conditions a drive display may show displacement power factor while a meter shows true power factor. Identify which label the plant specification calls for. Matching the angle of the voltage and current fundamentals alone may leave the two figures different.
- Range and configuration
- For sinusoidal waveforms, power factor relates to the cosine of phase angle, while reactive power is reported in var or kvar. Quote the wiring and sign convention.
- Manufacturers and models
- Rishabh's Rish Delta power-meter family illustrates electrical power derived from voltage and current. Identify the installed function as power factor or reactive power.
- What we check
- Compare the indication at known leading and lagging phase conditions. Include the voltage and current levels at which the scale is used.
- Reference equipment and accuracy
- Use a calibrated multiphase power source or reference power meter. For readings close to zero reactive power, phase uncertainty is especially important.
- When to repeat the check
- Reassess after CT reconnection, phase sequence changes or a new scaling factor.
Technical references Rishabh Rish Delta power-meter manual