Probe resistance or the paired display reading
Record the wiring arrangement and identify the display or transmitter normally connected. A probe-only result in ohms can be reused with another suitable reader, while a system result belongs to the particular sensor and readout tested together.
When replacing a building sensor, the transmitter configuration is as important as the connector. A spare marked Pt1000 should be recorded with the input type selected on the transmitter. Otherwise a wiring or configuration fault could be treated as an error in the new sensor.
Specifications and service checks
A Pt1000 has a nominal resistance of 1,000 Ω at 0 °C. A universal input left on its Pt100 setting expects 100 Ω at that temperature. After a probe change, compare the input selection with the nameplate before drawing conclusions from an implausible display.
- Range and configuration
- A Pt1000 has a nominal 1,000 Ω resistance at 0 °C. Identify the curve, connection and tolerance class of the installed element. Assembly construction determines the usable temperature range.
- Manufacturers and models
- WIKA documents Pt100 and Pt1000 resistance assemblies in its TR10 family. Confirm the element, tolerance class and wiring from the instrument record.
- What we check
- Compare the sensor with a reference thermometer and report resistance or temperature error at the required points. Include its wire configuration and any transmitter fitted in the head.
- Reference equipment and accuracy
- Use a calibrated platinum reference, controlled bath or block and a traceable resistance readout. A Class A or B label describes a tolerance envelope; a reference needs known uncertainty and corrections.
- When to repeat the check
- Track resistance at a repeatable check point. Mechanical shock, high-temperature service and a change in lead configuration are reasons to recheck sooner.